Intelligent management of battery health, early warning of faulty batteries.
Active ventilation and explosion venting design to control deflagration risks.
Multi-level electrical protection and fire protection design, with arc flash analysis and collaborative protection functions.
Modular design reduces failure impacts and improves system uptime.
Active balancing technology and bionic-inspired solutions enhance battery lifespan and system discharge capacity.
IEEE 693 high design level qualification compliance.
Back-to-back and side-by-side design reduces footprint.
All pre-assembled, no battery module handling on site.
Integrated AC/DC built-in bi-directional inverter, reducing commissioning time(for string pcs version).
Active balancing reduces energy storage station O&M costs.
Rapid state detection and fault recording to achieve rapid positioning and analysis of system faults.


| Cell Type |
LFP3.2 V / 314 A
|
| Battery Configuration |
1P416S*12
|
| Nominal Capacity |
5015.9kWh
|
| Battery Voltage Range |
1123.2~1497.6 V
|
| Nominal Battery Voltage | 1331.2 V |
| Nominal Power |
1290 kVA *2 (Aqua-C2.5S 5015-2500-2h) 1290 kVA (Aqua-C2.5S 5015-1250-4h) |
| Current THD | < 3% (nominal power) |
| DC Component | < 0.5% |
| Nominal Voltage |
690 V |
| AC Voltage Range | 607–759 V |
| Nominal Frequency |
60 Hz
|
| Termination (LV) |
1080 A * 3 Phase * 2 (Aqua-C2.5S 5015-2500-2h)
1080 A * 3 Phase (Aqua-C2.5S 5015-1250-4h)
|
| Power Factor | ≥0.99 (nominal power) |
| Power Factor Range | - 1 to +1 |
| Auxiliary Power Supply |
400VAC, 50Hz / 60Hz
480 V AC, 60 Hz
|
| Operating Ambient Temperature Range |
-30 °C to +55 °C (-22 °F to 131 °F)
|
| Relative Humidity | ≤ 100% RH (non-condensing) |
| Max. Operating Altitude |
4000 m (13123 ft)
|
| Ingress Protection (IP) Rating | IP55 |
| Temperature Control Method | Intelligent liquid cooling |
| Weight (approx.) |
44000 kg (97003 lb)
|
| Corrosion-proof Grade |
C4, C5 (optional) |
| Seismic Level |
IEEE 693 moderate design level qualification
IEEE 693 high design level qualification (optional)
|
| Snow Load |
30 lb /sqft
|
| Wind Load |
129 mph
|
| Dimensions (W × H × D) |
6058 × 2896 × 2438 mm (238.5 × 114.0 × 96.0 in)
|
| Fire Suppression System |
Fire alarm control panel, Smoke and heat detectors, Alarm bell, Horn strobe, Gas detector, Ventilation system (NFPA 69 compliance), Dry pipes with sprinklers, Aerosol (optional), Deflagration vent panel (optional)
|
| Communication Interface | Ethernet |
| Standard Compliance |
UL 9540A, NFPA 855, NFPA 69, NFPA 68 (optional), UL 1973, UL 9540, UL 1741SB, IEEE 1547
IEC62477-1, IEC62619, IEC61000, IEC62933, IEC63056, EN50549, G99, CEI 0-16, VDE-AR-N 4110, VDE-AR-N 4120,NTS 2.1, NTS SENP 1.1
|
|
|
|
|
|
©2026 Shenzhen CLOU Electronics Co., Ltd.
All rights reserved. Subject to change without notice. Version 1.0 02/2026
|
| Nominal Energy | 5015.9 kWh |
| Nominal Power |
2500 kW@0.5CP (Aqua-C2.5H 5015-2500-2h) 1250 kW@0.25CP (Aqua-C2.5H 5015-2500-4h) |
| Battery Voltage Range | 1123.2-1497.6 V |
| Nominal Battery Voltage | 1331.2 V |
| Cell Type | LFP 3.2V/314Ah |
| Battery Configuration | 1P416S*12 |
| Auxiliary Power Supply |
400VAC, 50Hz / 60Hz
480 V AC, 60 Hz
|
| SOC Calculation Accuracy | ≤ 3% (after balancing) |
| Operation Ambient Temperature Range | -30°C to +55°C (-22°F to 131°F) |
| Relative Humidity | ≤100% RH (non-condensing) |
| Max. Operating Altitude |
4000 m (13123 ft)
|
| Ingress Protection (IP) Rating | IP55 |
| Temperature Control Method | Intelligent liquid cooling |
| Weight (approx.) | 42600 kg (93917 Ib) |
| Corrosion-proof Grade |
C4, C5 (optional)
|
| Seismic Level |
IEEE 693 moderate design level qualification
IEEE 693 high design level qualification (optional)
|
| Snow Load | 30 lb /sqft |
| Wind Load | 129 mph |
| Dimensions (W × H × D) | 6058 × 2896 × 2438 mm (238.5 × 114.0 × 96.0 in) |
| Fire Suppression System | FACP, Smoke and Heat Detectors, Flammable Gas Detector, Horn strobe, Compliance Ventilation System, Dry Pipes with Sprinklers, Aerosol |
| Communication Interface | Ethernet (Fiber optional) |
| Standard Compliance |
UL 9540A, NFPA 855, NFPA 69, NFPA 68 (optional), UL 1973, UL 9540, UL 1741SB, IEEE 1547
IEC62933-5-2, EN62477-1, IEC61000, IEC62619, IEC63056, UN38.3/UN3536, CE |
|
|
|
|
|